10-1. List of specifications
SD-D58 Series
70
[SD-D58
・
DC
・
GH]
<
Taiwan Ex(TS) Specifications
>
Model
SD-D58
・
DC
・
GH
Detection principle
Semiconductor type
Detection gas
Combustible gas / toxic gas
Display
Seven-segment LED (four-digit)
Detection range
Depend on detection gas
Resolution
Depend on detection gas
Detection method
Sample-drawing
Flow rate
1.0 L/min or more (at maximum suction pressure of 5.0 kPa <gauge pressure>)
Alarm setpoints
Depend on detection gas
Power display
POWER lamp on (green)
External output
Gas concentration signal/alarm contact (gas alarm or fault alarm, gas/fault common
alarm)
Alarm accuracy (under the
same conditions)
Within ±25% to the alarm setpoint value (combustible gas)
Within ±30% to the alarm setpoint value (toxic gas)
Response time (under the
same conditions)
Within 30 or 60 seconds after providing the gas 1.6 times the alarm setpoint
(depends on the gas to be detected, excluding delay in the tube)
Gas alarm type
One-step alarm (H)
Gas alarm display
ALM lamp on (red)
Gas alarm pattern
Non latching (Auto-reset)
Fault alarm/self diagnosis
System abnormalities/sensor abnormalities/low flow rates
Fault alarm display
FAULT lamp on (yellow)/detail display
Fault alarm pattern
Non latching (Auto-reset)
Alarm contact
No-voltage contact 1a, de-energized (energized in response to an alarm) or energized
(de-energized in response to an alarm)
Contact capacity
250 VAC - 0.5 A/30 VDC - 0.5 A (resistant load)
Transmission system
three-wire type analog transmission (common cable for power and signal<power,
signal, common>)
Transmission specifications
4 - 20 mA DC (no-insulation/load resistance under 300
Ω
)
Transmission cable
Shielded cable of CVVS, etc. (1.25mm
2
or 2.0mm
2
) - 3-core (when the contact is not
used)
Shielded cable of CVVS, etc. (1.25mm
2
or 2.0mm
2
) - 5-core (when the contact is used)
Transmission distance
Less than 250m in case of CVV 1.25mm
2
Less than 450m in case of CVV 2.0mm
2
Functions Alarm
delay/suppression
Power supply
24 VDC ±10%
Power consumption
Maximum 8.7W
Cable connecting port
Pressure proof packing gland<G3/4>(Compatible cables
φ
9.0mm
~
φ
16.0mm in outer
diameter)
Tube connecting port
Rc1/8 (O.D
8-1t half-union for Cu tube <Bs> supplied or half-union for SUS tube
<SUS>)
Operating temperature
-20 - +53ºC (Non-rapidly-vary)
Operating humidity
Below 95% RH (Non-condensing)
Structure
Wall mounting type (2B<50A> pipe installation supported)
Explosion-proof structure
Flame-proof enclosures
Explosion-proof class
Ex d
Ⅱ
B+H2 T4 Gb
IP rating
Equivalent to IP67
Dimension
Approx. 197 (W) x 292 (H) x 140 (D) mm (projection portions excluded)
Weight
Approx. 5.8 kg
Outer color
Munsell 7.5BG5/2
* Specifications subject to changes without notice.
Summary of Contents for SD-D58-AC-GH
Page 1: ...PT2E 1758 Smart Transmitter Gas Detector Head SD D58 AC GH SD D58 DC GH Operating Manual ...
Page 4: ......
Page 6: ......
Page 7: ......
Page 8: ......
Page 9: ......
Page 13: ......
Page 14: ......
Page 15: ......
Page 17: ......
Page 19: ......
Page 20: ......
Page 21: ......
Page 22: ......
Page 23: ......
Page 24: ......
Page 26: ......
Page 27: ......
Page 28: ......
Page 29: ......
Page 30: ......
Page 31: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 35: ......
Page 36: ......
Page 38: ......
Page 39: ......
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 46: ......
Page 47: ......
Page 50: ......
Page 53: ......
Page 54: ......
Page 55: ......
Page 58: ......
Page 59: ......
Page 60: ......
Page 61: ......
Page 62: ......
Page 63: ......
Page 66: ......
Page 80: ......
Page 82: ......