Please note
System must be connected to open expansion tank for safety reasons.
Any valve must not be connected to safety input and safety output lines.
For increasing safety of the system, by-pass line must be installed on the line between input and output of
circulation pumps, as shown in diagrams.
By-Pass line's valve must be kept closed as the boiler is working normally.
By-Pass line's valve can be used in electricity problems and must be opened if there is a risk of overheating
in system water caused by an electricity cut or problem.
The pipe used in by-pass line must be at least in the diameter of plumbing systems pipe.
UPS (Power Supply Units) can be used for preventing electricity problems.
Please note
Any problems (malfunctions) caused by boiler clogging with dirt from the heating system and/or malfunctions
induced by clogging, are not covered by the boiler warranty.
Please note
The filter as well as the sludge trap must be checked and cleaned regularly.
Heating water requirements
Heating water requirements are specified in EN Standards. When the sum of concentrations of calcium and
magnesium in the water exceeds 1.8 mmol/l , additional non - chemical treatments preventing lime
deposition must be considered (e.g. Magnetic or electrostatic field treatment).
Boiler location
S.MAX boilers can be located both on non - habitable premises (e.g. in boiler room,cellar,corridor…) and in
habitable rooms. The room in which the boiler is located must have a permanent supply of air necessary for
the combustion process. The air must be free of halogen hydrocarbons and corrosive vapours, and must
not be excessively humid and dusty. The room must be protected against frost, with ambient temperature
within the range +5 °C to +35 °C and relative humidity not exceeding % 80.
To comply with fire regulations, the boiler must be installed:
• on floor constructed of non-flammable material
• on a non - flammable material overlapping the boiler footprint by 20 mm on each side and covering the
entire depth of the boiler body.
• if the boiler is installed in a cellar, we recommend to put it on a socket at least 50 mm high, positioning the
boiler in the middle
boiler in the middle
To comply with standarts, at least 600 mm manipulation space must be left in front of the boiler. Minimum
distance between the back of the boiler and the wall must be also 600 mm, and a free space of at least
600 mm must be left between one side of the boiler and the wall, to allow access to the rear of the boiler.
Fuel must not be stacked directly behind on next to the boiler at a distance less than 800 mm.
If there are two boilers in the boiler room, no fuel is allowed to be stacked between them. We
recommend to keep a minimum distance of 800 mm between the boiler and fuel (
Fig. 16
), or keep
fuel in a room other than the one in which the boiler is installed.
* Do not put flammable materials on top of the boiler or near the boiler than specified safety
distance.
18
Summary of Contents for S.MAX Series
Page 1: ...S MAX SERIES SOLID FUEL BOILER S MAX SERIES SOLID FUEL BOILER 0 S MAX REV 01 2010 0036 0036...
Page 4: ...Boiler dimensions Boiler packaging dimensions 3...
Page 5: ...Technical parameters 4...
Page 17: ...fig 12 fig 13 fig 14 fig 15 16...
Page 22: ...SMAX boiler parts fi 18 fig 18 fig 19 21...
Page 23: ...Spare parts list p p fig 20 22...