Boiler Dimensions for ONGAS 300/W
Plumbing Instructions
·
Return water inlet, gas inlet and supply water outlet connections placed in rear side of the boiler.
·
Every model (ONGAS 303/W,304/W, 305/W, 306/W, 307/W) has a different water and gas connection
size. Boiler connection sizes are given in the technical table.
·
Avoiding of the faulty circulation, check valves must be used with circulation pump system. In the new /old
buildings and new/old plumbing systems, strainer (filter) must be used in the return water line.
·
Safety valve (max.6 bar), and manometer must be used in the plumbing system. There must not be any
valve between boiler and safety valve, otherwise pipes and the other parts may explode in the over-
pressurized boiler (evaporation harmless).
·
RIMA ONGAS 300/W Series Condensing Boilers are only compatible and works with systems which has
circulation pump.
·
RIMA ONGAS 300/W Series Condensing Boilers delivered without circulation pump.
·
RIMA ONGAS 300/W Series Condensing Boilers are compatible with max. 6 bar systems.
Heating (Radiator) Water
Sanitary water can be used for plumbing and additional
water. Please clean the plumbing system before filling
with water. Chemical materials and softeners can cause
damage to system.
Please consider on the standards and instructions while
the plumbing system are installing, otherwise water
leakage or plumbing problems will occur.
For avoiding the Oxygen diffusion to radiator water ( may cause
from the problem in the heat exchanger), system separator should be used in the system.
Supply
Water
Outlet
Return
Water
Inlet