Gas Connections
·
Gas connections must be done by authorized personnel or gas certificated plumbing
companies.
·
Old plumbing systems, must be refined from sediment and debris before installation of
radiator and gas piping.
·
Gas side connections must be checked against gas leakage before commissioning.
·
Poisoning and explosion risk due to inappropriate gas plumbing materials using and installation
is not made in accordance with the rules.
·
Fire protected gas valve must be used in the system, if not, risk of explosion in case of firing.
·
Gas connections must be done according to standards and directives.
Perform the gas leakage test, when the check valve is OFF. Gas valves can be exposure max. 150 mbar
pressure. Gas valves and burners may damaged over this pressure and as a result of explosion and
poisoning. In the pressure test of gas side, ball valve in gas device must be closed (OFF position).
Please be careful of gas type that using in the boiler and please consider on the conversion instructions.
Electrical Connections
·
Electrical connections must be done by authorized technicians.
·
Terminal box, fuse, switches and sensors delivered completely assembled and functionally tested.
·
Main supply and other accessories (circulation pump, etc…) must be connected
by
authorized technicians.
·
Please examine carefully the electrical wiring diagram, before making any connection.
·
Please cut off the electrical ( main ) supply , before any operations. The electrical supply is not
cutted, when the ON/OFF switch is at OFF position.
Flue Gas
Measuring
Point
Fresh Air
Intake
Chimney
·
In the flue gas discharge connections, only RIMA Original Parts and authorized local gas dealer parts must
be used. Please read carefully instructions before connecting the chimney.
·
Local gas distributers may have different directives, because of this, information should be taken from local
gas companies and dealers.
Gas Inlet