Combustion System Check
Combustion is checked by measuring the O
2
/CO
2
percentage in the flue gas discharge duct. To do this, heat the boiler to a
water temperature of ~ 70°C. The measurements must meet the values set
according to gas rate adjustments. The flue gas
temperature can also be measured at the measuring point in the flue gas discharge duct. If the flue gas temperature exceeds
the return temperature by more than 30°C, this can indicate that the heat exchanger is dirty.
Cleaning the modulated fan , venturi and burner
1. Cut off the electrical supply.
2. Close the main gas valve.
3. Remove the electrical connections from the fan, gas valve and electrodes.
4. Remove the bolts from the venturi-air inlet connection.
5. Remove the pressure sensor and temperature sensor cables.
6. Remove the bolts from venturi-gas inlet connection.
7. Remove the burner connection bolts from heat exchanger.
8. Clean the pre-mix burner with air gun (nozzle - burner distance approx. 1 cm- compressed air must be 2 - 4 bar).
9. Remove loose dust from the fan and burner.
10. Clean the venturi pipe with a plastic brush or air.
11. Re-assemble all removed components; check the correct positioning of the sealing plate between fan and venturi.