2.3 P-TRAP
The indoor coil incorporates an evaporator drip tray and is supplied with a 20mm Female Pressure Pipe drain
spigot, which is to be connected to the “P” trap (supplied).
•
Always install the “P” trap as close to the unit as possible.
•
Fill the “P” trap with water during installation before starting unit, to prevent air movement through the drainpipe
•
Ensure trap contains water at all times
•
Adjust the level of the unit to ensure that the condensate drains from the evaporator drip tray (approx 10 - 15mm
incline from back to front)
2.4 OUTDOOR UNIT
Figure 5. Outdoor Unit Major Components
Figure 3. “P” Trap Assembly
Figure 4. “P” Trap Assembly
Electric Panel
3 phase Contactor
3 Phase Power Supply
Fan Run Capacitors
HP Switch
LP Switch
Liquid Line Service
Ball Valve
Liquid Filter Drier
Suction Line Service
Ball valve
Scroll Compressor
Suction Accumulator