Rinnai Corporation EX17 / EX22 Manual
Extension
Installation
Kit
CAUTIONS
INCORRECT
Too many bends (limit is 2)
Air intake hose is above exhaust pipe.
Condensed water
may accumulate
here, and cause a blockage
preventing combustion.
Condensed water formed by
combustion, will run back to the
unit, and may overflow from the
condensation pan if pipes are
longer than 10 feet. Therefore, pipes
exceeding these lengths should be
made to drain to the outside by
giving their horizontal portions 3˚ or
more downward and outward slope.
3˚ slope(approximate)
Less than 10 ft.
CAUTION
Never allow the exhaust pipe
to sag, as condensed water
may accumulate and cause
incomplete combustion.