Neo RIB2312 installation guide: 12148-A 01-17
Freestanding direct and offset flueing
M
inimum of 3
.6 m, maximum of 8 m
500 mm min.* clearance from any
part of the building, refer p. 30
Clearances from combustibles 10 mm (to allow
for contraction and expansion of the flue pipes)
45 ° bend, maximum of
two per installation
Wall penetration kit
Flue is built from the ground up. Refer ‘installation
overview PDF for the Neo Freestanding flue kits
on www.rinnai.co.nz.
* The end of the flue shall be at least 500 mm from the nearest part of the chimney (AS/NZS 5601.1 6.9.2 (a))