26
INSTALLATION INSTRUCTIONS
Water Connection
For all closed systems (with flow and return or tank) the system must incorporate an
unvented kit with the components shown below. The safety relieve valve must discharge
safely into a suitable drain via a tundish.
Gas Connection
Refer to BS6891 (Natural Gas) and BS5482 (Propane) for guidance on correct pipe sizing
calculation. There must be 20 mbar Natural Gas (G20) or 34.5 mbar Propane (G31) at the
inlet of the appliance with all appliances at high fire.
Electrical Connection
The heater electrical supply must be installed to the latest I.E.E. regulations. If the unit is
hard wired (moulded plug removed) it must be provided with a fused (5A) local isolator with a
contact separation of 3mm minimum on all poles for servicing. Observe polarity and ensure
that wiring is correctly restrained.
Isolation
Valve
Y- Strainer Pressure
Reducing
Valve with
Gauge
Double
Check
Valve
Expansion
Vessel
Safety
Relief
Valve
Tundish
Mains
Summary of Contents for R E U - K M2635FFUDHD-E
Page 20: ...20 OPERATION Infinity K32e and HDC1500e Infinity K32i and HDC1500i...
Page 21: ...21 OPERATION Infinity K26e and HDC1200e Infinity K20i K26i HDC1000i and HDC1200i...
Page 33: ...33 CONDENSATE DISPOSAL...
Page 42: ...42 DIMENSIONS Infinity K32i and HDC1500i Infinity K32e and HDC1500e...
Page 43: ...43 DIMENSIONS Infinity K20i K26i HDC1000i and HDC1200i Infinity K26e and HDC1200e...
Page 49: ...49 FLOW CHART...
Page 50: ...50 WIRING DIAGRAM Infinity K32 5 amp...
Page 51: ...51 WIRING DIAGRAM Infinity K20 K26 5AMP FUSE...
Page 52: ...52 DIAGNOSTIC POINTS Infinity K20 K26 Infinity K32 Y Y...
Page 53: ...53 WATER FLOW CHARACTERISTICS Infinity K32 Infinity K20 K26...
Page 54: ...54 LETTER OF COMPLIANCE...
Page 55: ...55 CE CERTIFICATE...
Page 56: ...56 CE CERTIFICATE...
Page 58: ...58 COMMISSIONING SHEET...
Page 59: ...59 SERVICE RECORD...