3.1 PARAMETERS MENU
For safety reasons, it is advisable not to modify the parameters of the menus without having fully
understood the meaning of the parameters themselves and the consequences produced on the
boiler.
It is recommended to always contact Rinnai Italia in advance so as not to damage the boiler or the
plant to which it is connected and to exclude potential risks for the user.
parameter unit of measurement
The value of the displayed parameter is shown on the right side of the WiFi
thermostat display:
- the value is expressed in hundreds (1 = 100);
- the value is expressed in units.
parameters of b menu
The B menu mainly collects the parameters relating to the use of the boiler:
Nr
par.
Parameter
Values
Parameter description
Unit /
Default value
1
Gas type
1~4
1: NG - G20; 2: Propane - G31;
3: Air/Propane - G230; 4: GPL - G30.
2
Hours of combustion in
CH mode
0~1999
Total hours of operating in CH.
1 = 100h
3
Hours of combustion in
DHW mode
0~1999
Total hours of operating in DHW.
1 = 100h
4
Flame failure during
operation
0~1999
Total flame failures during combustion.
5
Burner ignitions in CH
mode
0~1999
Total burner ignitions in CH.
1 = 100 times
6
Burner ignitions in mode
DHW
0~1999
Total burner ignitions in DHW.
1 = 100 times
7
Black-out
0~1999
Total detected black-out .
1 = 10 times
8
Gas consumption in CH
mode
0~1999
Total gas consumption in CH.
1 = 100
(m
3
or Kg)
9
Gas consumption in
DHW mode
0~1999
Total gas consumption in DHW.
1 = 100
(m
3
or Kg )
10
Power limiter CH
Min~100%
The boiler power is limited to the set % value,
de-powering the CH function only (range rated boiler).
100%
11
Modulating pump
ON/OFF
Pump operation: modulating flow or max.
ON = modulating operation / OFF = max
ON
12
Pump activation
ON/OFF
OFF: pump active during combustion;
ON: pump always active.
OFF
13
Switching time
DHW-CH 3-way valve
ON = 30 sec
OFF = 3 min
Waiting time of the 3-way valve before switching from
DHW to CH after the use of hot water.
OFF
14
Room thermostat type
A = closed
B = open
Type of contact of the room thermostat.
(Closed contact = heat request with closed circuit)
B
15
Hearthquake sensor
ON/OFF
Activate / deactivate the earthquake sensor.
ON
16
Chimney sweep function
ON/OFF
Activate the boiler at max power for ten minutes.
OFF