• © 2009 Rinnai America Corporation
37
Boiler Parameters
(in relation to the RS100)
Parameter Chapter
PARA
Default
Range
Description
RS100 Note
1
176
°
68 to176
°F
Maximum supply temp in
heating mode
This will
override the RS100’s setting if
lower (UC PARA 13)
2
00
01-04
Curve preset for type of heat
emitters-see reset curve slide
This is not overridden
—but should still
be set from the RS100
5
2.3
0.2-3.5
K Factor of outdoor reset curve
(this depends on PARA 2)
The RS100 heat curve button and/or UC
PARA 27 overrides this setting
6
1.4
1.1-1.4
Outdoor reset curve exponent
RS100 overrides this setting
7
14
°F
-4
°F to 32°F
Outdoor reset curve coldest
design day setting
RS100 System PARA 9 overrides this
setting
10
0
°
-8
°F to 10°F
Day temperature calibration
(outdoor reset curve)
RS100 will override these settings
—no
parameter is available or needed to do
so as it is constantly sampling the room
and adjusts as needed
11
0
°
-8
°F to 10°F
Night temperature calibration
(outdoor reset curve)
•
When using an RS100, the only adjustment that must be made at the boiler is PARA
73
—most others can be made at the RS100
•
Boiler parameter 2 or 14 may need to be set to establish an appropriate gradient
control line (the defualt is 10
°F/min)
• When connecting an RS100, please observe the following notes at each parameter: