5
alarm setting procedures are as follows:
Step1. High temperature setting: Press the “OK Key” for 2 seconds then the Receiver Beeps
twice to get into the temperature alarm setting mode. The Display shows “HI” and
the Default figures flashing on it.
Step2. Press “Right Key” or “Left Key” to adjust the alarm temperature setting. The
temperature is adjusted by 0.5
℃
(or 1
℉)
a time such as 38.5,39,39.5 and so on, then
press “OK Key” to finish setting.
Step3. Low temperature setting: Repeat Step1, press the “OK Key, ” when the “HI” and the
Default figures flashing on it, to get into the “LO” and the Default figures flashing on
the Display.
Step4. Press “Right Key” or “Left Key” to adjust the alarm temperature setting (see Step 2).
Note:
®
The Default
:
The Default figures of the temperature alarm setting are HI
:
38
℃
and LO
:
34
℃
( or HI
:
100
℉
and LO
:
93
℉
) and the Receiver will take these figures as the
Temperature Alarm Setting without any change in advance. The high
temperature alarm ranges from 32 to 42
℃
( or 96 to 104
℉
); the low
temperature alarm ranges from 32 to 34.5
℃
( or 89 to 96
℉
).
®
Unintentionally Pressing function
:
The receiver will return to the temperature monitoring
mode and without change any setting if the operations mentioned above are
not finished within 10 seconds.
®
Priority Alarm processing
:
The product is designed to process the alarm situation prior to the
temperature alarm setting model, or any other operations. Without saving any
setting if not pressing the “OK Key. ” the operator is better off to operate
temperature alarm setting with the full power supply.
®
Please re-set the High/Low temperature alarm setting after replacing the batteries, or the
Receiver will get the default as the temperature alarm setting.
w
Check the High/Low temperature alarm setting:
The figures of “HI” and “LO” on the LCD Display show the setting of the High/Low
temperature alarm set by the operator.