3.2.6 PQ Event Settings
3.2.6.1 Sag Threshold Setting
After entering in the “PQ EVENT SETTINGS”, List of following options
will be displayed :-
3.2.6.1 SAG THREHOLD
3.2.6.2 SWELL THRESHOLD
3.2.6.3 SAG & SWELL HYSTERESIS
3.2.6.4 OVERCURRENT THRESHOLD
3.2.6.5 OVERCURRENT HYSTERESIS
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
CT SECONDARY
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
DATALOGGING OPTIONS
MAIN
SETUP
EVENT BASED DATALOG
TIME BASED DATALOG
LOAD PROFILE DATALOG
Here 0 to 9 digit input keypad is provided to set the Sag Threshold &
user can confirm this value with a simple touch on “ key” and
cancel the change by touching the “ key”.
The valid range is
10 to 90 % of nominal voltage
.
If value outside this range is entered, it will display “INVALID VALUE”
followed by correct range of parameter.
ENTER
BACK
ENTER SAG THRESHOLD IN %
SAG THRESHOLD
0
.
3.2.6.2 Swell Threshold Setting
Here 0 to 9 digit input keypad is provided to set the Swell Threshold &
user can confirm this value with a simple touch on “ key” and
cancel the change by touching the “ key”.
The valid range is
110 to 150 % of nominal voltage
.
If value outside this range is entered, it will display “INVALID VALUE”
followed by correct range of parameter.
ENTER
BACK
ENTER SWELL THRESHOLD IN %
SWELL THRESHOLD
0
.
The value decides the threshold for swell detection.
(Refer section 8 for details)
The value decides the threshold for sag detection.
(Refer section 8 for details)
Note
: Changing Swell Threshold would erase the Swell data of PQ events.
Note
: Changing Sag Threshold would erase the Sag data of PQ events.
39