Pub. 1147 - Rev. 7 SEPTEMBER 2004
29
Mechanical Dock Leveler Hydraulic Conversion
NORMAL VOLTAGE AND AMPERAGE
WIRE SIZES / GAUGE CHART - SINGLE PHASE
Note
Variation of line voltage will offset motor performance. 120 volt single phase
motors will be very sensitive to low voltage.
The wire gage chart expresses the
recommended wire size that should
be used for Rite Hite
®
Hydraulic
Levelers. The chart takes into account
the phasing and voltage of the power
unit, and the distance the wire is run
from the leveler to the main power
source (circuit breaker, or fused
disconnect)
Motors Incoming Line Voltage Starting Voltage Starting Amps Minimum
Running
(from electrical sources) Running Voltage
Amps
120 Volt - 1 Phase
110
14
115
7 to 14
208 Volt - 1 Phase
200
7
205
4 to 7
230 Volt - 3 Phase
220
5.5
220
3.8 to 5.5
460 Volt - 3 Phase
440
3.2
440
1.9 to 3.2
Motor
Single Phase
Single Phase
(Power Units)
120) Volts
208-230 Volts
Distance
0-100 Ft.
Min.12 gauge
Min.12 gauge
Between
Leveler 100-200 Ft.
Min.10 gauge
Min.12 gauge
Control Box
and Power
200+ Ft.
Min.10 gauge
Min.12 gauge
Source
(Circuit
Breaker)
WIRE SIZES / GAUGE CHART - THREE PHASE
Fused Service
208-230V, 3Ph.,60 Hz
380V, 3Ph., 60 Hz. 460V, 3Ph., 60 Hz. 575V, 3 Ph., 60Hz
7 Amp.
5 Amp.
4 Amp.
3 Amp.
Dual Element Fused Dual Element Fused Dual Element Fused Dual Element Fused
Minimum Wire
0-100 Ft.
10 Gage Wire
10 Gage Wire
10 Gage Wire
10 Gage Wire
Gage
Requirements
100-200 Ft. 10 Gage Wire
10 Gage Wire
10 Gage wire
10 Gage Wire
From Power
Source To
200+ Ft.
10 Gage Wire
10 Gage Wire
10 Gage Wire
10 Gage Wire
Service
Disconnect