NOTE:
Make sure to route the cable so that it does not
interfere with the installation of the motor shroud.
If the flexible conduit is too long for the
installation, cut the protective outer casing and
leave 16" to 20" of wires. Do not connect the
conduit to the fitting on the control box until
correct conduit and wire length is achieved.
Local electrical codes may require the use of rigid
conduit, rather than flexible conduit. If required,
remove the control cables from the furnished
flexible conduit, install the rigid conduit in its place
and rewire. Make sure to remove and replace the
conduit connector in the bottom of the control box.
7. Drill a hole for the power supply cable (by others) in the
bottom of the control box using the proper connection to
maintain the NEMA rating on the enclosure.
All holes
drilled through the control box must be through the
bottom of the box.
8. Connect wiring as indicated by the device field wiring
located on
Pages 23-25.
Incoming 3-phase power must
connect into terminals L1, L2, and L3. Ground must attach
to the green/yellow terminal.
NOTE: Route all field installed wires so that separation is
maintained between line voltage wires and low
voltage class II wiring. Electrical prints included in
the parts or control box, supersede any prints
included in this owners manual on
Pages 23-25.
Always check parts or control box for prints.
Pub. No. 8000CLB FEBRUARY 2004
9
PROTECDOR® CL Model 8000CL
CONTROL BOX INSTALLATION
FIGURE 14
GND L3 L2 L1
F2 F1 F4 F3 S4 S2 S3 S1 B2 B1 W V U GND
Top Pot Switch
is Reclose
Timer, Lower is
Preannounce
Illuminated
Input LED’s
Illuminated
Output LED’s
Illuminated
Run/Power
LED’s
Hand Held
Programmer
Receptacle