background image

1 Application 

Rittal cooling unit assembly and operating instructions  

page 

3

 of 

13

 

1

 

Application 

Enclosure  cooling  units  are  designed  and  built  to 
dissipate  heat  from  enclosures  by  cooling  the  air 
inside  the  enclosure  and  protecting  temperature 
sensitive components. 

2

 

Technical data 

See nameplate  

3

 

Assembly 

The standard wall-mounted unit is suitable for exter-
nal  mounting. Cut  out the  sections  and  drill  accord-
ing to the drawing.  
Cut  the  enclosed  seals  to  the  required  length  and 
attach  to  the  unit.  Screw  tapped  pins  into  the  blind 
nuts  on  the  rear  of  the  unit.  The  unit  is  then  to  be 
secured using washers and nuts 

4

 

Safety notes 

The  following  safety  notices  are  to  be  observed  in 
their entirety for the correct use of the equipment: 
 

 

To  prevent  the  enclosure  with  the  cooling  unit 
fitted  tipping  over,  it  is  essential  that  this  be 
bolted to the floor. 

 

A  roller  door  is  to  be  used  to  ensure  problem 
free opening and closing of the enclosure door.  

 

A  transportable  enclosure  with  built-in  cooling 
unit  may  only  be  produced  if  an  additional 
transport  anchorage  to  support  the  cooling  unit 
is used.  
Prior to mounting, ensure that:  

 

the  site  for  the  enclosure,  and  hence  the  ar-
rangement to the cooling unit, is selected so  as 
to ensure good ventilation;  

 

the location is free from excessive dirt and mois-
ture,  

 

the  cutout  for  air  extraction  is  located  in  the 
upper area of the enclosure; 

 

the  mains  connection  ratings,  as  stated  on  the 
rating plate. are available:  

 

the  ambient  temperature  does  not  exceed 
+50°C;  

 

The  packaging  shows  no  signs  of  damage. 
Traces  of  oil  on  damaged  packaging  are  an  in-
dication of refrigerant loss and of leakage in the 
unit system. Any damage to the packaging may 
be the cause of subsequent malfunctions:  

 

the 

enclosure 

is 

sealed 

on 

an 

sides              

Condensation will occur if the enclosure is leaky;  

 

the separation of the units from one another and 
from the wall should not be less than 200mm;  

 

air  inlet  and  outlet  are  not  obstructed  on  the 
inside of the enclosure;  

 

units  are  only  fitted  horizontally  in  the  specified 
position Max. deviation from the true horizontal: 
2°  

 

condensate drainage is provided  

 

electrical  connection  and  repair  are  carried  out 
only by authorized personnel  

 

Use  only  original  replacement  parts  and  acces-
sories.  

 

Losses  from  the  components  installed  in  the 
enclosure  must  not  exceed  the  specific  refrige-
ration capacity of the cooling unit itself;  

 

The customer may not modify the cooling unit in 
any way. 

5

 

Commencing operation and 
control behavior 

Following the completion of mounting and a  waiting 
period  of  approximately  30  minutes  (to  allow  oil  to 
collect in the compressor in order to ensure lubrica-
tion and cooling). 

5.1 

Controller control 

 

Figure 1: Controller 

 
After  electrical  connection  the  internal  fan  turns  on 
and  circulates  the  enclosure  air.  This  helps  assure 
even  temperature  distribution  within  the  enclosure. 
The  condenser  fan  and  compressor  are  controlled 
by the controller. The minimum time is 3 minutes to 
restart the compressor after it has switched off. The 
switching difference is 5 K. To avoid short switching 
cycles  and  hence  the  danger  of  inadequate  or  only 
partial  cooling  in  some  sections  of  the  enclosure, 
The switching difference should be set to be only as 
low  as  necessary.  For  economic  reasons  (energy 
saving),  the  nominal  value  of  the  internal  enclosure 
temperature Ti should also be set to be only as low 
as necessary. 

5.1.1

 

Operation of the controller 

The  display  terminal  H1  consists  of  a  3  position  7-
segment  display  which  indicates  the  internal  enclo-
sure  temperature  in  °C  as  well  as  any  fault  codes. 
The  actual  enclosure  internal  temperature  is  con-
stantly displayed on H1. When a system message is 
generated,  this  alternates  in  the  display  with  the 
current internal enclosure temperature. 

Summary of Contents for 1194.42 Series

Page 1: ...Assembly and operating instructions Compact cooling unit 3370 22X 3370 52X 3370 32X 3370 62X 3370 37X 3370 72X 3370 42X 1194 42X 1194 55X 1194 62X 1194 72X ...

Page 2: ... Display buttons 5 5 1 8 Compressor On Off 6 5 2 Alarm parameters 6 5 3 Evaluating system messages 6 5 4 Forced cooling 6 6 Filter mats 6 7 Technical informations 7 7 1 1 Operation of the cooling unit 7 7 1 2 Condensate discharge 7 8 Handling instructions 7 8 1 Fitting the cooling unit 7 8 1 1 External mounting of the cooling unit 8 8 1 2 Partial internal mounting of the cooling unit accessories n...

Page 3: ...ill occur if the enclosure is leaky the separation of the units from one another and from the wall should not be less than 200mm air inlet and outlet are not obstructed on the inside of the enclosure units are only fitted horizontally in the specified position Max deviation from the true horizontal 2 condensate drainage is provided electrical connection and repair are carried out only by authorize...

Page 4: ...ours C A0 Alarm and fan differential 20 20 2 See chapter 5 2 F AH Alarm maximum temp 50 99 10 See chapter 5 2 C Ad1 Delay for high and low temp alarm 0 199 30 Delay for high temperature alarm when power on just before When alarm condi tion is achieved but power on just before the timer start to count for a specify value Ad1 Only the time elapsed alarm relay can be active 5 1 3Parameter navigation ...

Page 5: ...button to access the password setting use the UP and DOWN buttons to scroll the numbers until displaying 22 password to access the parameters press the SET button to confirm the password use the UP and DOWN buttons to scroll the pa rameters press SET to display the value associated with the parameter increase or decrease the value us ing the UP or DOWN button respectively press SET to temporarily ...

Page 6: ...emperature message may also be polled via a contact on the connection clamp of the cooling unit system message relay with changeover contact see connection diagrams Terminal 1 C connection of the supply voltage to the fault signal relay Terminal 2 NO normally open Notice Delay for high temperature alarm when power ON When alarm condition is achieved but power is ON the timer start to count for a s...

Page 7: ...of the refrigerant rises above the ambient temperature and heat can be dissipated to the envi ronment via the surface of the condenser Then the refrigerant is liquefied and by means of a thermos tatically controlled capillary returned to the evapora tor where it evaporates at low pressure The heat required for complete evaporation is drawn from the enclosure interior causing it to cool down The co...

Page 8: ...y along the back of the unit so that no gaps are left at the joints Figure 8 Applying the self adhesive tape Screw the supplied grub screws into the blind nuts on the rear of the unit Secure the unit using the supplied washers and nuts Figure 9 Securing the unit all compact units except 3370220 8 1 2Partial internal mounting of the cooling unit accessories not in cluded Fix the 4 mounting bars on ...

Page 9: ...y for use at sites with a continuous current carrying capacity incoming mains power supply of more than 100 A per phase and with a supply voltage of 400 230 V If necessary the electricity supply company must be consulted to ensure that the continuous current carrying ca pacity at the point of connection to the public grid is sufficient for connection of such a unit The fans and compressors in sing...

Page 10: ...ntensity Notice Caution Risk of fire Never use flammable liquids for cleaning Sequence of maintenance measures Check the level of dirt Filter soiling Replace the filter if necessary Cooling membranes soiled Clean if necessary Activate test mode cooling function OK Check noise generation of compressor and fans Sequence of maintenance measures Check the level of dirt Filter soiling Replace the filte...

Page 11: ...e 19 Twist off the screw of the outside fan 1 Figure 20 Twist off the screw of the outside fan 2 Figure 21 Remove the outside fan Figure 22 Disconnect the plug of the outside fan 1 Figure 23 Disconnect the plug of the outside fan 2 Figure 24 Clean the heat pipe and compressor chamber using compressed air ...

Page 12: ... Rittal plant Please contact us for advice 11 Scope of supply and guaran tee 1 cooling unit ready for connection 1 sealing tape 1 set of mounting and operating instructions Guarantee This unit is covered by a 1 year guarantee from the date of supply subject to correct usage see also Safety notices under heading 4 Within this period the returned unit will be repaired in the factory or replaced free...

Page 13: ...RITTAL GmbH Co KG Postfach 1662 D 35726 Herborn Phone 49 0 2772 505 0 Fax 49 0 2772 505 2319 E mail info rittal de www rittal com ...

Reviews: