background image

5 Commencing operation and control behavior 

page 

4

 of 

13                                                              

Rittal cooling unit assembly and operating instructions 

 

 

5.1.2

 

Editable parameters 

 

Param. 
Type 

Display 
screen 

Parameter 

Min. 
value 

Max. 
value 

Factory 
setting 

Description 

PS 

Password 

99 

22 

Protection code for modifying the configu-
ration parameters (default=22). The value 
of the password can be customized from 
the supervisor 

St 

Setpoint 

r1 

r2 

35 

:r1 minimum value and r2 maximum 
value of the set point. Parameter St de-
termines the desired temperature to be 
maintained inside the cabinet or cold 
room (set point). 

rd 

Regulation diffe-
rential 

+19 

Value that is added to (or subtracted 
from, i

n „reverse‟ mode) the temperature 

set point. 

rd= low values:

 

 

more precise temperature control; 

 

high compressor On/Off switching 
frequency in the event of minimum. 
Temperature deviations (with the risk 
of causing damage). 

rd= high values:

 

 

less precise temperature control; 

 

low compressor On/Off switching 
frequency in the event of minimum 
temperature deviations. 

Important:

 the compressor can also be 

safeguarded using the parameters that 
limit the number of activations/hour and 
the minimum off time 

r1 

Setpoint min. 
value 

20 

r2 

30 

r1  & r2 :set the range of  temperatures 
for setting the set point. 

r2 

Setpoint max. 
value 

r1 

50 

45 

cc 

Continuous cycle 
period 

15 

1 (hours) 

A0 

Alarm and fan 
differential 

-20 

+20 

See chapter 5.2 

AH 

Alarm maximum 
temp. 

-50 

+99 

10 

See chapter 5.2 

Ad1 

Delay for high and 
low temp. alarm 

199 

30 

Delay for high temperature alarm when 
power on just before. When alarm condi-
tion is achieved but power on just before , 
the timer start to count for a specify value 
(Ad1). Only the time elapsed, alarm relay 
can be active 

5.1.3

 

Parameter navigation 

The  operating  parameters, modifiable  using  the  key-
pad, are divided into two types: frequent (type F) and 
configuration  (type  C).  Access  to  the  latter  is  pro-
tected by password (default= 22) to prevent acciden-
tal or un-authorized modifications. 

Accessing the type F parameters:

 

 

Press the SET button for more than 3 s (if there 
are active alarms, mute the buzzer), the display 
shows the parameter code „PS‟ (password);  

 

use the UP and DOWN buttons to scroll the pa-
rameters. The LED corresponding to the catego-
ry of parameters will be on (see parameters list) 

 

 

press SET to display the value associated with 
the parameter increase or decrease the value us-
ing the UP or DOWN button respectively;  

 

press SET to temporarily save the new value and 
display the parameter again; repeat the proce-
dure for any other parameters that need to be 
modified;  

 

press the SET button for more than 3 s to per-
manently save the parameters and exit the pa-
rameter setting procedure.  

Accessing the type C parameters:

 

 

Press the SET button for more than 3 s (if there 
are active alarms, mute the buzzer), the display 
shows the parameter code “PS” (password);  

Summary of Contents for 1194.42 Series

Page 1: ...Assembly and operating instructions Compact cooling unit 3370 22X 3370 52X 3370 32X 3370 62X 3370 37X 3370 72X 3370 42X 1194 42X 1194 55X 1194 62X 1194 72X ...

Page 2: ... Display buttons 5 5 1 8 Compressor On Off 6 5 2 Alarm parameters 6 5 3 Evaluating system messages 6 5 4 Forced cooling 6 6 Filter mats 6 7 Technical informations 7 7 1 1 Operation of the cooling unit 7 7 1 2 Condensate discharge 7 8 Handling instructions 7 8 1 Fitting the cooling unit 7 8 1 1 External mounting of the cooling unit 8 8 1 2 Partial internal mounting of the cooling unit accessories n...

Page 3: ...ill occur if the enclosure is leaky the separation of the units from one another and from the wall should not be less than 200mm air inlet and outlet are not obstructed on the inside of the enclosure units are only fitted horizontally in the specified position Max deviation from the true horizontal 2 condensate drainage is provided electrical connection and repair are carried out only by authorize...

Page 4: ...ours C A0 Alarm and fan differential 20 20 2 See chapter 5 2 F AH Alarm maximum temp 50 99 10 See chapter 5 2 C Ad1 Delay for high and low temp alarm 0 199 30 Delay for high temperature alarm when power on just before When alarm condi tion is achieved but power on just before the timer start to count for a specify value Ad1 Only the time elapsed alarm relay can be active 5 1 3Parameter navigation ...

Page 5: ...button to access the password setting use the UP and DOWN buttons to scroll the numbers until displaying 22 password to access the parameters press the SET button to confirm the password use the UP and DOWN buttons to scroll the pa rameters press SET to display the value associated with the parameter increase or decrease the value us ing the UP or DOWN button respectively press SET to temporarily ...

Page 6: ...emperature message may also be polled via a contact on the connection clamp of the cooling unit system message relay with changeover contact see connection diagrams Terminal 1 C connection of the supply voltage to the fault signal relay Terminal 2 NO normally open Notice Delay for high temperature alarm when power ON When alarm condition is achieved but power is ON the timer start to count for a s...

Page 7: ...of the refrigerant rises above the ambient temperature and heat can be dissipated to the envi ronment via the surface of the condenser Then the refrigerant is liquefied and by means of a thermos tatically controlled capillary returned to the evapora tor where it evaporates at low pressure The heat required for complete evaporation is drawn from the enclosure interior causing it to cool down The co...

Page 8: ...y along the back of the unit so that no gaps are left at the joints Figure 8 Applying the self adhesive tape Screw the supplied grub screws into the blind nuts on the rear of the unit Secure the unit using the supplied washers and nuts Figure 9 Securing the unit all compact units except 3370220 8 1 2Partial internal mounting of the cooling unit accessories not in cluded Fix the 4 mounting bars on ...

Page 9: ...y for use at sites with a continuous current carrying capacity incoming mains power supply of more than 100 A per phase and with a supply voltage of 400 230 V If necessary the electricity supply company must be consulted to ensure that the continuous current carrying ca pacity at the point of connection to the public grid is sufficient for connection of such a unit The fans and compressors in sing...

Page 10: ...ntensity Notice Caution Risk of fire Never use flammable liquids for cleaning Sequence of maintenance measures Check the level of dirt Filter soiling Replace the filter if necessary Cooling membranes soiled Clean if necessary Activate test mode cooling function OK Check noise generation of compressor and fans Sequence of maintenance measures Check the level of dirt Filter soiling Replace the filte...

Page 11: ...e 19 Twist off the screw of the outside fan 1 Figure 20 Twist off the screw of the outside fan 2 Figure 21 Remove the outside fan Figure 22 Disconnect the plug of the outside fan 1 Figure 23 Disconnect the plug of the outside fan 2 Figure 24 Clean the heat pipe and compressor chamber using compressed air ...

Page 12: ... Rittal plant Please contact us for advice 11 Scope of supply and guaran tee 1 cooling unit ready for connection 1 sealing tape 1 set of mounting and operating instructions Guarantee This unit is covered by a 1 year guarantee from the date of supply subject to correct usage see also Safety notices under heading 4 Within this period the returned unit will be repaired in the factory or replaced free...

Page 13: ...RITTAL GmbH Co KG Postfach 1662 D 35726 Herborn Phone 49 0 2772 505 0 Fax 49 0 2772 505 2319 E mail info rittal de www rittal com ...

Reviews: