Rittal enclosure heater assembly instructions

5

5 Electrical connection

EN

4

Mounting

The heater is fitted vertically, i.e. with the con-
nection terminal or fan facing downwards. To 
permit the required convection, a minimum 
clearance to the adjacent components must 
be observed. A safety clearance of at least 
300 mm must be left at the air outlet in the 
case of heaters with fans, and 100 mm for 
heaters without fans. (For both heaters a ther-
mal safety clearance to the sides of 60 mm 
and 100 mm at the bottom is required). If 
these clearances are observed, the ambient 
temperature at the air inlet does not rise 
above 65°C. 

There are two different methods of 
assembling the heater:
1. Snap-type fastening onto a 35 mm support 

rail DIN EN 50 022 (fig. 2).

2. Screw fastening onto the mounting plate 

(fig. 3).

It should be ensured that the heater and 
connection cables are mounted firmly and 
securely. 
Electric cables must not touch the body of 
the heater fan and must not be routed directly 
past the hot air outlet. 
The heater must not be mounted in the 
vicinity of flammable materials.

5

Electrical connection

The heater must be connected, via the quick-
connect terminals, to a power supply of the 
voltage stated on the rating plate. 
The heater must be connected to the 
mains via an all-pole isolating device in 
accordance with the overvoltage category III 
to EN 60 664-1. Only copper wires are to be 
used for the electrical connection. Due to 
the special characteristics of the PTC heater 
element, a current of up to 4.4 A may be 
reached for a short time when the heater is 
switched on. 
Slow-blowing fuse-links (gG) or circuit-
breakers with a corresponding delayed-trip 
characteristic can be used as pre-fuses. The 
required pre-fuse rating is specified on the 
rating pate. Overvoltage protection is to be 
provided where pulse loads exceeding 
1,000 V are possible. The double connection 
terminal permits the cascading of several 
heaters and thus simplifies wiring. In such 
cases, it may be necessary to adapt the pre-
fuse rating to accommodate the total start-up 
current. The maximum switching capacity of 
the devices must nevertheless be observed. 

Note:

In justified, exceptional cases, 
heaters with fan (235 – 870 W) 
may be installed rotated through 
180°. 
Please note that, in case of 
mounting on a 35 mm support 
rail, the mounting clips must also 
be rotated through 180°.

Summary of Contents for 3105.310

Page 1: ...KJtage eJ bedieJiJgshaJdHeidiJg KJtage Kch haJteriJgsaJvisJiJg IstruViKJi di IKJtaggiK e fuJViKJaIeJtK IJstrucciKJes de IKJtaFe 取扱説明書 SchaHtschraJG HeiVuJg EJcHKsure heater RËsistaJces chauffaJtes SchaGeHGastverwarIiJgeJ VÇrIeeHeIeJt f r apparatsGÈp RiscaHdatKre aJticKJdeJsa ResisteJcia caHefactKra エンクロージャー用ヒーター 3105 XXX ...

Page 2: ...E certification 3 1 3 Storing the documents 3 1 4 Symbols used 3 2 Safety notes 3 3 Device description 4 3 1 Functional description 4 3 1 1 How it works 4 3 1 2 Control 4 3 2 Proper use 4 3 3 Scope of supply 4 4 Mounting 5 5 Electrical connection 5 6 Storage and disposal 6 7 Warranty 6 8 Technical specifications 6 9 Dimensions 7 ...

Page 3: ...ts constitute an integral part of the product They must be given to the plant operator The operator is responsible for storage of the documents so they are readily available when needed 1 4 Symbols used 2 Safety notes When performing the electrical installation it is important to observe all valid national and regional regulations as well as the provisions of the responsible electrical supply comp...

Page 4: ... 3110 000 or a digital thermostat 3114 200 must be used to con trol the enclosure temperature The humidity of the air in the enclosure can be controlled by incorporating a hygrostat 3118 000 3 2 Proper use Rittal heaters were developed and designed in accordance with the state of the art and the recognised rules governing technical safety Nevertheless if used improperly they may pose a threat to l...

Page 5: ...ls 5 Electrical connection The heater must be connected via the quick connect terminals to a power supply of the voltage stated on the rating plate The heater must be connected to the mains via an all pole isolating device in accordance with the overvoltage category III to EN 60 664 1 Only copper wires are to be used for the electrical connection Due to the special characteristics of the PTC heate...

Page 6: ...5 330 3105 340 3105 350 3105 360 3105 370 Dimensions in mm W H D 45 120 46 45 120 46 64 155 56 64 155 56 64 230 56 90 165 75 90 180 75 Hole distance mm 42 60 Rated operating voltage 110 240 V AC 50 60 Hz 110 240 V DC Continuous thermal output W at Tu 10 C 8 10 18 20 23 30 49 50 63 75 86 100 130 150 Ambient temperature 33 C 65 C Pre fuse T 2 A 4 A Protection category IP 20 Protection class II We re...

Page 7: ...IN EN 50 022 Fig 3 Screw fastening onto a mounting plate Hole distance Hole distance for fitting rotated through 180 Note In case of assembly rotated through 180 the mounting clips must always point upwards A B 3105 310 3105 370 1 x 3105 310 3105 340 2 x 3105 350 3105 370 3105 380 3105 430 A A max 6 mm B 9 Dimensions ...

Page 8: ...8 Rittal enclosure heater assembly instructions 9 Dimensions EN Fig 4 Removal of the units 1 2 3 4 ...

Page 9: ...130 2 111 2 17 2 59 8 59 8 59 8 3105 380 3105 430 SK II N L u SK II N L u M 1 3105 310 3105 370 3105 380 3105 430 110 240 V AC 50 60 Hz DC 115 240 V AC 50 60 Hz Fig 5 Wiring plan Heater Fig 6 Wiring plan Heater with fan Fig 7 Fastening onto a mounting plate Fastening possibilities on support rails ...

Page 10: ...6 3 108 3 66 3 108 3 75 8 94 8 a b 3105 310 320 3105 330 340 3105 350 360 370 Fig 8 Fastening onto a mounting plate Fastening possibilities on support rails Fig 9 Fastening onto a mounting plate Fastening possibilities on support rails Fig 10 Fastening onto a mounting plate Fastening possibilities on support rails ...

Page 11: ...no A4407400SK73 䡲 Enclosures 䡲 Power Distribution 䡲 Climate Control 䡲 IT Infrastructure 䡲 Software Services RITTAL GmbH Co KG Postfach 1662 䡠 D 35726 Herborn Phone 49 0 2772 505 0 䡠 Fax 49 0 2772 505 2319 E mail info rittal de 䡠 www rittal com ...

Reviews: