11 Inspection and maintenance
EN
66
Rittal Liquid Cooling Package
11
Inspection and maintenance
The Liquid Cooling Package is largely maintenance-
free. An additional external filter should be used if the
cooling water is contaminated. This should be
cleaned regularly.
– The condensate discharge device should be
checked regularly for proper function.
– Visually inspect for leaks regularly (annual cycle).
Note:
At an ambient temperature of 40 °C, the
nominal service life of the built-in fan is
40,000 operating hours.
Fan module malfunctions are displayed on
the optional display or on the status screen
of the CMC III PU (if the Liquid Cooling
Package is connected to a network). Further-
more, the built-in control that is responsible
for two fan modules compensates fully in the
event of a fan module failure.