5 Assembly and siting
EN
Grasp the fan module with both hands on the left
and right, and pull it out between the upper and low-
er air baffle plate.
5.3.2
Installing a fan module
As supplied, all rack mounts not fitted with a fan are
sealed with a metal cover. For units not fully populated
with fans, these metal covers ensure separation into a
hot and cold air zone inside the device, for targeted air
routing.
Configuration with LCP Rack and LCP Inline:
Disconnect the earth connection on the metal cover
(fig. 33, item 3).
Loosen the two screws, right and left (fig. 33,
item 1), used to secure the metal cover in the rack
mount at the top and bottom.
Remove the metal cover (fig. 33, item 2) from the
rack mount.
Fig. 33:
Metal cover – LCP Rack and LCP Inline version
Key
1
Screws
2
Metal cover
3
Earthing cable connection
Place the fan module on the shelf rotated through
90° (fig. 30) and push it into the rack mount.
Rotate the fan module through 90° in a counter-
clockwise direction so that the connection cables
are pointing towards you.
Secure the fan module to the mounting plate at the
top and bottom using two screws, left and right.
On the left and right, insert one of the fan connectors
into the corresponding socket on the Liquid Cooling
Package.
Make the earth connection to the fan.
At the fuse box, re-connect the thermally activated
switch for the pair of fans of which one fan has been
replaced.
Activate the newly installed fan in the software (see
section 8.2.4 "LCP configuration").
Configuration with LCP Inline flush:
Disconnect the earth connection on the metal cover
(fig. 34, item 3).
Loosen the two screws at the top and bottom
(fig. 34, item 1) used to secure the metal cover in the
rack mount.
Remove the metal cover (fig. 34, item 2) from the
rack mount.
Fig. 34:
Metal cover – LCP Inline flush version
Key
1
Screws (4 x)
2
Metal cover
3
Earthing cable connection
Place the fan module rotated through 90° (fig. 32)
between the upper and lower air baffle plate and
push the module into the rack mount.
Rotate the fan module through 90° in a counter-
clockwise direction so that the connection cables
are pointing towards you.
Secure the fan module to the mounting plate at the
top and bottom using two screws, left and right.
On the left and right, insert one of the fan connectors
into the corresponding socket on the Liquid Cooling
Package.
Make the earth connection to the fan.
Note:
The installation site of individual fan modules
may be varied according to the load.
Caution! Risk of injury!
Before installing or removing a fan, be
sure to remove the power from the rele-
vant group of fans on the corresponding
thermally activated switch.
1
2
3
1
1
1
2
3
1
1