Rittal Liquid Cooling Package
69
13 Technical specifications
EN
Tab. 35: Technical specifications for 30 kW versions
13.1.2 LCP Inline flush
Other information
Temperature control
Linear fan control/2-way control valve
TO
Air
[°C (°F)]
+6 to +35 (+43 to +95)
TS
Air
[°C (°F)]
+6 to +35 (+43 to +95)
Noise level [dB(A)]
(Open air above reflective flooring, distance 1 m)
77
Technical specifications
Technical specifications
Description/Model No.
TopTherm LCP Inline flush / 3311.148 (1050 mm depth)
Description/Model No.
TopTherm LCP Inline flush / 3311.548 (1200 mm depth)
Dimensions and weight
Dimensions width x height x depth (mm)
300 x 2000 x 1050 (3311.148) or 1200 (3311.548)
Usable U
42
Weight, max. [kg]
220
Electrical connection
Type of electrical connection
Connector
Rated voltage [V, Hz]
208/2~ 50/60
230/1~ 50/60
Rated current [A] (2 fans)
4.3
3.9
Max. current [A] (4 fans)
9.6
8.1
Pre-fuse [A] (4 fans)
16
16
Duty cycle [%]
100
Cooling output
Number of fans
2
3
Cooling output [kW]
18
27
Power consumption P
el
[kW]
Max. 1.8 at 100% fan speed
Air throughput, max. [m
3
/h]
4800
Protection category
IP 20
Cooling circuit
Cooling medium
Water (see Internet for specifications)
Coolant inlet temperature [°C]
+15
PO
H2O
[bar (psi)]
2 to 6 (29 to 88)
PS
H2O
[bar (psi)]
6 (88)
PT
H2O
[bar (psi)]
12 (175)
Fill quantity [l]
7
Water connection
1½" outer thread