4.7. Battery Replacement PMC12
compact
Step 1:
Step 2:
Step 3:
Step 4:
Note!
Was the used battery of the UPS
System removed during normal
operation this will not immediately
be recognized by the PMC12
because after the startup the UPS
will check only sporadically
(approx. every 60 min.) if there is a
battery connected.
Danger!
Do not nip in the ups during a
change of batteries. Some parts
can be under voltage!
Warning!
The lead acid battery may cause
chemical hazard.
The battery presents a risk of
energy hazard.
Do not dispose of batteries in a fire.
The batteries may explode.
Do not open or mutilate batteries.
Released electrolyte is harmful to
skin and eyes. It may be toxic.
Note!
Servicing of batteries should be
performed or supervised by
personnel knowledgeable about
batteries and required precautions.
When replacing batteries, replace
with the same type and number of
batteries or battery packs