Technical Specifications
UPS-Manual
30
EN
Environmental
Operation Temperature*
0 - 40 °C
Noise Level
< 50 dBA
Relative Humidity
0 to 90% (Without condensation)
Interface
Interface Type
1x USB port, 1x RS-232 port, 1x Slot for Communication Card
SNMP
Power management from SNMP manager and Web browser
Compatible platforms
Windows 95/98/NT/2000/XP/Vista, Novell NetWare, Linux, etc.
Standards and Certification
Safety
IEC/EN 62040-1-1,IEC 60950-1
Performance IEC/EN
62040-3
EMC
IEC/EN62040-2 Class A, FCC Part 15 Subpart B Class A,
IEC/EN55011, CISPR11, IEC61000-4-2/-3/-4/-5, IEC61000-2-2,
IEC61000-3-2/-3
Markings CE,
WEEE
*NOTE: Is the UPS running in an environment with temperatures over 40°C this will lead to a
clear shortened life-time of the batteries. In some cases this can cause damage on the batteries
and the UPS.
Model 1KVA
2KVA
3KVA
Backup Time with Extended Battery Module
Load
100% >28min.
>17min.
>12min.
80% >35min.
>24min.
>17min.
60% >55min.
>32min.
>24min.
40% >110min.
>50min.
>37min.
1 extended Battery
module
20% >155min.
>105min.
>88min.
Load
100% >55min.
>29min.
>20min.
80% >68min.
>38min.
>26min.
60% >96min.
>51min.
>35min.
40% >144min.
>86min.
>58min.
2 extended Battery
modules
20% >300min.
>175min.
>127min.