Installation
UPS-Manual
11
EN
4.2. Selecting Installation Position
Warning!
The UPS is heavy.
Select a location sturdy enough to handle the
UPS weight. To ensure proper operation and
long operating life, always position the UPS
according to the following criteria:
Keep minimum 20cm (8 inches) distance
clearance from the rear panel of the UPS to
avoid any obstructions.
Do not block the air-flow to the ventilation
louvers of the unit.
Please ensure the installation site is free from
excessive dust and the ambient temperature
and humidity should be within the specified
limits.
Do not place the UPS in a dusty or corrosive
environment or near any flammable objects.
This UPS is not designed for outdoor use.
Note!
The batteries inside the external
packages of these ups can have a
strengthened gas emission of
hydrogen in case of a fire or
technical fault. Please refer to EN
50272-2 for references for battery
ventilation.
C
0
0
C
40
0
Relative Humidly
(non condensing) 30%~90%
20cm