Technical Data
UPS-Manual
28
EN
11. Technical
Data
Model
4,5 kVA
6 kVA
INPUT
Voltage Window
160~280 VAC*
Frequency
45 ~ 65 Hz
Phase/Wire
Single, Line + N Ground
Power Factor
Up to 0.99 at 100% Linear Load
Current THD
<6% at 100% Linear Load
OUTPUT
Voltage Window
220/230/240 VAC Selectable
Voltage Adjustment
0%;
±
1%;
±
2%;
±
3%
Voltage Regulation
±
2%
Capacity
4500 VA / 3600 W
6000 VA / 4800 W
Rated Power Factor
0.8 Lagging
Wave Form
Sine Wave, THD<3%(no load to full Linear load)
Frequency Stability
±0.2%(Free Running)
Frequency Regulation
±1%; ±3%
Transfer Time
0ms
Efficiency(AC to AC, Normal)
Up to 90%
Efficiency(AC to AC, ECO)
Up to 97%
Autonomy at load
50%
100%
50%
100%
1 Battery
20 Min.
9 Min.
18 Min.
8 Min.
2 Batteries
48 Min.
23 Min.
45 Min.
20 Min.
3 Batteries
95 Min.
39 Min.
74 Min.
33 Min.
DC Start
Yes
BATTERY
Type
Sealed Lead Acid Maintenance Free
12 V / 7 Ah
Quantity
20 pcs
Voltage
240 VDC
Recharge Time
4 hours to 90%