Rittal Power distribution unit PDU basic
Depending on the PDU version, provide the following pre-fuse:
Route the PDU connection cable out of the IT rack and connect it to the mains supply.
Connect one connection cable from the Rittal accessories to a free slot on the PDU and the equip-
ment.
Depending on the PDU version, unused slots can be closed using the C13/C19 covers from the avail-
able accessories (7955.010 and 7955.015).
If installation is not successful: see section 1.1.
6
Technical specifications
6.1
General technical specifications
PDU basic:
3 x 16 A (16 A versions) or 3 x 32 A (32 A versions)
Note:
When connecting the equipment, please note the maximum load per PDU slot (C13:
10 A; C19: 16 A; Earthing pin (CEE 7/3): 16 A; BS 1363 (UK): 13 A).
Technical specifications
Temperature application range
Temperature Operation: +5 °C…+50 °C (at 100% load))
Temperature Storage: -20 °C…+70 °C
Humidity application range
10%…95% relative humidity, non-condensing
Protection category
IP 20 to IEC 60 529
Protection class
1
Overvoltage category
II
Degree of contamination
2
max. operating height
3,000 meters above sea level
min. operating time
100,000 h
EU conformity
Low-Voltage Directive 2014/35/EU
EMC Directive 2014/30/EU
IEC/EN 62368
Input voltage range (L – N)
90 V…260 (400) V AC, 50…60 Hz
Input current
16 A/32 A (depending on variant)
No. of phases
1 or 3 depending on PDU variant
Colour coding of the phases/fuse circuits
(3-phase versions only)
L1: pink
L2: black
L3: white
Connection cable type
H05-VV
No. of wires
3/5 (single-phase/3-phase PDU)
Allocation of fuses, phases and slots, Installation and operation