Rittal PDU metered/metered plus/switched/managed
25
EN
3.4
Base configuration
As standard, the PDU is activated to automatically obtain an IPv4 address from a DHCP server in the
network. If no DHCP server is available, the following base configuration is preset:
If the PDU cannot be included in the network with these settings, they can be changed via the display
or the PDU website (see Section 6).
4
Assembly notes
The PDU is assembled using the brackets supplied loose as accessories. As a general rule, assembly
may be carried out either from the front or back, or from the left or right of the IT rack.
Compact horizontal PDUs are designed for installation within the 482.6 mm (19") level. The required
assembly components for simple mounting are included with the supply. Depending on the type and
design of the IT rack, the PDU may also be fitted at the side of the 482.6 mm (19") level, as well as
vertically on the frame section of the IT rack. In such cases, additional assembly components may be
required which are
not
included as part of the PDU supply.
5
Installation and operation of the PDU
5.1
Operating and display elements
The operating and display elements are shown in fig. 12. The display direction and the assignment of
the four keys at the side next to the display depends on the installation direction of the PDU. The key
to fig. 12 shows the key assignment for the installation case with electrical connection of the PDU at
the bottom. If the PDU is installed with the electrical connection at the top, the assignment of keys 1
and 5 as well as 2 and 4 is reversed. The actual assignment of the keys is shown correctly on the dis-
play.
IP address:
192.168.0.200
Netmask:
255.255.255.0
Gateway:
0.0.0.0
Security PIN:
1221
Speeds
Ethernet 1 and 2 (RJ 45):
10 / 100 / 1000 Mbit/s
Note:
Rittal recommends always attaching the brackets to the PDU first, and then securing the
assembled unit to the inside of the enclosure. This means that the distances between the
brackets and hence the mounting points inside the enclosure are pre-defined, allowing
you to promptly identify any potential collisions of the PDU inside the enclosure.
Note:
Select the mounting point (position and spacing) for the two universal supports inside the
enclosure so they match those of the fastening pieces mounted on the PDU.
Product description, Assembly notes, Installation and operation of the PDU