11.2.14
Checking the function of the door contact switch
Check whether the door contact switches including the magnets are firmly mounted.
Check whether the door contact switch switches safely.
11.2.15
Checking the blocking switch
As soon as the blocking switch of the system is set to "Agent disconnect [blocked]",
the yellow LED (top right) on the front panel lights up.
11.2.16
Checking for proper connection of the transmission
A pending failure (e.g. via blocking switch or door contact switch) can be transmitted
to a permanently manned location. This function is to be checked.
11.2.17
Checking whether shutdown occurs
Signals for the shutdown of external electrical devices (e.g. fans) can be transmitted
via the potential-free relay outputs. Check whether shutdown of the external devices
is functioning.
11.2.18
Reading out and transferring data
Read out and archive the data of the system for every maintenance and installation.
Chapter 10.3 “Project” on page 94
describes how customer data can be read out
and changed.
11.2.19
Checking the electrical connections
L
WARNING!
Risk of death or severe physical injury due to electric shock!
Check and repair where applicable the electrical connections of the system
and the connections to the additional electrical devices that are connected.
11.2.20
Cleaning the pipe system
NOTICE
Property damage from compressed air!
Compressed air can damage components and fire detectors.
● Never blow into the system with compressed air.
Maintenance
Operating Instructions / DET-AC III Master / 916005 / 11-2022 / en_US