This networking is to be checked with the removal of the mains lead and, where
applicable, corrected. If any changes are made, they must be reported.
11.2.25
Changing the filter
The used filter (Fig. 82/1) is released from
the hoses and the new filter is put into
exactly the same position.
11.2.26
Checking for contamination in the housing
Removed any contamination in the housing (e.g. dust, lint).
11.2.27
Checking loss monitoring
To check the function of the loss check, the
system must be connected electrically and
raised on the right hand side at an angle of
roughly 20°.
➩
In the display (Fig. 83/1) the message
“Extinguishing agent loss”
is shown.
INFORMATION
Set the filter time for the check to zero; reset it to the set value afterwards.
11.2.28
Power supply
L
WARNING!
Risk of death or severe physical injury due to electric shock!
Fig. 82: Filter
Fig. 83: Loss monitoring
Maintenance
Operating Instructions / DET-AC III Master / 916005 / 11-2022 / en_US
108