1 Connection loss monitoring
2 Tank
3 Propellant cartridge
4 Ignition plug
5 Earthing screw
6 Threaded union nozzle pipe
11.3.1
Safety instructions for the tank change
L
WARNING
Danger for insufficiently qualified personnel!
Insufficiently qualified personnel is incapable of assessing the risk involved when
changing the tank and may cause severe or fatal injuries to themselves or others.
● The removal of an empty tank after a release and the installation of a new full
tank may only be performed by trained personnel using the materials and tools
intended for the task.
L
WARNING
Risk of death due to electric shock!
An imminent risk of death or severe physical injury due to electric shock exists if
live components are touched.
● Allow only qualified electricians to work on electrical components and the elec-
trical connection.
● Disconnect the system from the power supply:
– Remove the mains lead.
– Remove all electrical connections.
– Actuate the battery button "Battery OFF".
L
WARNING
Danger due to high pressure!
The propellant cartridge of the release unit is pressurized in an unreleased state at
620 bar (8992 psi). Severe physical injury can result from damage to a pressure
hull in an unreleased state.
● Allow only trained personnel to handle and install a new full tank.
Fig. 85: Overview tank
Maintenance
Operating Instructions / DET-AC III Master / 916005 / 11-2022 / en_US
111