L
WARNING
Danger of reignition if devices are not shut down!
In order to prevent reignition, it is imperative that there is an energy shutdown of
the devices within the protected enclosure when the extinguishing system is
released.
● Use the floating contacts (Fig. 19/1 to 3) for the device shutdown that is to be
realized by the operator.
● If shutdown upon release is not guaranteed, it is necessary to make sure that a
manual fire fighting or shutdown measure, which
– prevents reignition, is completed within the hold time of the extinguishing
concentration,
or
– that an automatic shutdown of the devices is completed in order to prevent
reignition.
Fig. 19: Potential-free contacts
INFORMATION
Make sure, at an early stage, that the cabinet to be protected meets all of the
requirements in regard to space needs, tightness and mounting options, so that the
system can be installed in a proper functional manner.
INFORMATION
Be sure to keep the packaging the system came in. The system can only be sent
for maintenance or repair in the special original packaging it came in or in pack-
aging equivalent to this.
6.2.1
Installation instructions
L
WARNING
Danger due to faulty installation!
Non-horizontal installation of the system results in the extinguishing agent not being
fully discharged and the failure message
“Extinguishing agent loss”
being dis-
played.
● Mount the system in a horizontal position (using a spirit level for alignment).
Assembly and installation
Operating Instructions / DET-AC III Master / 916005 / 11-2022 / en_US
37