29.
Check the fault and alarm functions
Chapter 6.2.8 “Checking the failure and
30.
Chapter 6.2.8.4 “Fire detectors” on page 50
31.
Following the reaction test, wait at least two minutes for the concentration of
test gas in the fire detectors to fall.
32.
Reset the alarm with the upper
[Reset]
33.
Check that the "Extinguishing system triggered" LED (Fig. 25/1) is not illumi-
nated.
34.
L
WARNING! Risk of faulty release!
Activating the system: Switch the blocking switch (Fig. 20/arrow) to "Agent con-
Ⅰ
).
ð
The system is ready for operation and activation!
35.
Attach the "Gas-based extinguishing system – Danger to health!" sign (Fig. 26)
in a clearly legible position on the cabinet.
You should preferably attach the warning signs to the outside of the cabinet
doors. Alternatively, you can also attach the warning signs on a side wall if they
will draw more attention there.
Chapter 6.3 “Installation and commissioning of
additional electrical devices” on page 51
Fig. 24: [Reset] button
1
Fig. 25: "Extinguishing system trig-
gered" LED
Fig. 26: Warning sign
Assembly and installation
Operating Instructions / DET-AC III Master / 916005 / 11-2022 / en_US