6.2.5.2
Mounting the suction pipe
Fig. 35: Mounting
1.
[Fig. 35/1]: Mark the insertion depth (Fig. 35/H) of the pipe (Fig. 35/X). Use the
auxiliary line at the pipe angle. Insertion depth (H) approx. 33 mm.
2.
[Fig. 35/2]: Loosely insert the pipe.
3.
[Fig. 35/3]: Push in the pipe up to the marking (Fig. 35/X) and until it can be
heard and felt to be in the stop.
6.2.5.3
Disassembling the suction pipe
Fig. 36: Dismantling
1.
[Fig. 36/1]: Press down the retaining element (Fig. 36/a). The retaining element
is only recognizable as a ring from the outside.
2.
[Fig. 36/2]: Pull out the pipe when the retaining element is pushed down
Assembly and installation
Operating Instructions / DET-AC III Master / 916005 / 11-2022 / en_US
46