Connect the manual call point as per
Chapter 6.3.7 “Manual call point”
Reset the failure message that comes up
when connecting with the upper
[Reset]
button (Fig. 43/1).
After the manual call point is released, the lower red LED (Fig. 43/2) blinks and
“Manual release”
and
“Fire”
are shown in the display.
Reset the manual call point and activate the system again with the upper
[Reset]
button.
NOTICE
Faulty release due to removal of the blocking!
Premature removal of the blocking can result in a faulty release and thereby cause
property damage.
● Do not stop blocking the system until there are no red LEDs lit up and there is
no fire alarm shown in the display.
6.2.8.4
Fire detectors
L
CAUTION
Danger of injury from faulty release!
Checking the fire detector when the system is not blocked can result in a faulty
release. A faulty release may cause injuries and significant property damage.
● Block the system prior to checking the fire detector. To this end, switch the
blocking switch on the back of the system to the
Ⅱ
"Agent disconnect [blocked]"
position.
● Switch the blocking switch (Fig. 44/arrow) on the rear side of the system to
"Agent disconnect [blocked]". In this way the release mechanism for the propel-
lant cartridge is deactivated.
● Release the system using test gas (
Chapter 12 “Spare parts, accessories,
consumables, and tools” on page 116
) at the last hole of the suction pipe (spray
for approx. 2 to 4 seconds directly into the suction hole).
Fig. 42: Connection manual call point
Fig. 43: LED and [Reset] button
Assembly and installation
Operating Instructions / DET-AC III Master / 916005 / 11-2022 / en_US