The set monitoring range is moved as a whole (lower and upper threshold simulta-
neously).
The set monitoring range is moved as a whole by the calculated average using the
arrow buttons
“Monitoring range raise”
/
“Monitoring range lower”
.
Example:
For the set values to become effective,
they must be adopted
([Reset PS] button arrow).
8.6.3
Setting the integration time for the air flow monitoring (filter time)
Increase filter time
Abort function
Decrease filter time
Adopt current value
When the system is installed in air-conditioned cabinets, it can happen that the air
flow exceeds or falls below the set thresholds for a short time. An integration time
(filter time) can be set in seconds in order to avoid a failure.
If an arrow button is pressed for longer than three seconds, the value goes up auto-
matically. Due to the type of communication between the main processor and the
control panel, there is a slight delay between actuation of the button and the reaction
of the system. This means that when a button is released, which was previously
held pressed, the value is raised or lowered again by roughly 2. It is only then that
the automatic function is deactivated.
The value is set to 0 by pressing the buttons
and
at the same time.
Fig. 73: Setting prior to manual calibra-
tion (example)
Fig. 74: Setting after manual calibration
(+5)
Fig. 75: [Reset PS] button
Display and control elements