14
Technical data
Installation dimensions
19”, 44 mm (1.73 in.) [1 RU], 660 mm (26 in.) mm deep (depth
above everything)
Housing material
Sheet metal
Weight
Approx. 15.5 kg (34.17 lb.)
Nominal voltage
100 ... 240 V AC, 50/60 Hz
Emergency power
supply
Approx. 4 hr
Maximum battery
internal resistance
1200 mOhm
Maximum permissible
active current
1.0 A at 24 volts (the sum of all the connected devices must not
exceed the permissible active current of 1.0 A)
Maximum permissible
charge current
350 mA at 24 volts
Power supply unit load
currents:
I
maxa
/ I
maxb
1.3 A
I
min
Approx. 100 mA
Ambient temperature
+10 °C ... +40 °C (+50 °F ... +104 °F) [operating]
-20 °C ... +65 °C (-4 °F ... +149 °F) [storage without batteries]
-15 °C ... +40 °C (+5 °F ... +104 °F) [storage of batteries]
Humidity
Up to 96% relative, non condensing
Protection type
IP 30
Technical data
Operating Instructions / DET-AC III Master / 916005 / 11-2022 / en_US
120