6.2.5
Suction pipe installation instructions
L
CAUTION
Malfunction due to covered suction bores!
If any cables are covering the suction bores the smoke suction pipe system, fires
may not be detected and extinguished in good time. Any malfunction results in a
risk of injury and substantial property damage.
● Always discuss the installation of the system with the operator.
● If you subsequently fit cables in the protected cabinet, always ensure that the
suction bores remain unobstructed.
INFORMATION
The suction pipe system is a self-sealing and self-locking pipework system. The
pipe connection is fully established by connecting the pipe and fitting.
1.
Mount the vertical suction pipe (Fig. 31) in the cabinet at a point that is suitable
for the fluidic system using the clamps.
The suction bores must not be covered by the clamps or other add-on parts.
Fig. 30: Blocking switch
Fig. 31: Suction pipe
Assembly and installation
Operating Instructions / DET-AC III Master / 916005 / 11-2022 / en_US
43