L
CAUTION
Danger of injury due to escaping extinguishing agent!
If, when the system is blocked (display
“Extinguishing system blocked”
), a fire
alarm is released and blocking is removed when there is an alarm by, for example,
closing the door, the extinguishing process is released one second after blocking is
removed.
● Do not stop blocking the system until there are no red LEDs lit up and there is
no fire alarm shown in the display.
6.3.5.1
"RJ12 plug" door contact switch
Door contact input "5" (Fig. 52/5) is designed for the
Rittal
"RJ12 plug" door contact
5
13
Fig. 52: Connections for door contact switches
1
2
3
2
Fig. 53: Installation diagram
1
Door contact input "5" (Fig. 52/5)
2
"RJ12 plug" door contact switch (access sensor)
X1 RJ12 bushing (6-pin) for connecting to the system or for series connection with
an additional door contact switch
X2 RJ12 bushing (6-pin) for series connection with additional door contact
switches (maximum of 10 switches) or for the "terminating resistor" RJ12 plug
3
"Terminating resistor" RJ12 plug