INFORMATION
For 19" cabinets with automatic door opening "ADO", also observe the installation
Chapter 6.2.6 “Instructions for the use of the
DET-AC III Master system with simultaneous use of an automatic door opening
6.3.6
Combination of systems
When combining systems DET-AC III Master (Part No. 7338.121), DET-AC III Slave
(Part No. 7338.321) and EFD III (Part No. 7338.221) to protect several switch cabi-
nets, different settings must be made to the systems.
To this end, observe the operating instruction DET-AC III Slave and EFD III as well.
6.3.6.1
Compatibility of systems from different series
Systems DET AC Plus Slave of the old series (Part No. 7338.320) can as a general
rule be connected to active extinguishing systems DET-AC III Master of the new
series (Part No. 7338.121). In the same way, systems DET-AC III Slave of the new
series (Part No. 7338.321) can as a general rule be connected to active
extinguishing systems DET AC Plus Master of the old series (Part No. 7338.120).
The systems are fully functional. However, not all messages are transmitted and
certain functions cannot be performed (e.g. Maintenance Program, external
tank, ...).
6.3.6.2
Networking systems
Up to five systems (active extinguishing system DET-AC III Master or EFD III with
DET-AC III Slave) can be networked with each other via a bus system to protect
several switch cabinets. One data line and one supply line respectively must be laid
Chapter 6.3.6.4 “Connecting the energy supply and data line”
Assembly and installation
Operating Instructions / DET-AC III Master / 916005 / 11-2022 / en_US