8.12.1
Extinguishing agent monitoring filter time
Confirm change
Abort function
Abort function
Abort function
Increase filter time
Abort function
Decrease filter time
Adopt current value
If the value "Extinguishing agent monitoring" is at "0", a loss message from the
sensor is reported to the extinguishing agent monitoring immediately. If the value is
at "1" or higher, this number states the minutes that the loss message must remain
pending, without interruption, before a an extinguishing agent loss is recognized and
shown on the display.
8.12.2
Battery change
The operating time of the battery is monitored by a timer. If the battery exceeds the
maximum permissible operating time, a corresponding message indicator is shown
in the display and the system goes into failure state. There are the following options
for resetting this monitoring after a battery change:
● Battery change via the display
● Open the "Battery change" function
● Battery change using the Maintenance Program
.
Previous menu item
Exit menu
Next menu item
Activate submenu
After launching the function, this query occurs:
Display and control elements
Operating Instructions / DET-AC III Master / 916005 / 11-2022 / en_US