53
Operating and Maintenance Instructions – 6 Installation – "Getting Started"
Rittal Liquid Cooling Package Plus
The following standard sensors can be connected in addition:
Tab. 4:
List of standard sensors
6.6.2 Operation in stand-alone
mode
In stand-alone mode, the Liquid Cooling Package Plus is operated via the
touchscreen of the graphical display on the front door.
The user interface of the touchscreen allows the user to navigate between the
individual menu options of the Liquid Cooling Package Plus controller using
software-controlled buttons (MENU, NEXT, BACK).
Fig. 47:
Touchscreen
The following menu options can be accessed:
Sensor
Model No.
DK
Max.
Quantity
Temperature sensor
7320.500
4
Humidity sensor
7320.510
4
Analogue sensor input module "4 - 20 mA"
7320.520
4
Access sensor
7320.530
4
Vandalism sensor
7320.540
4 x 5
Airflow sensor
7320.550
4
Smoke alarm
7320.560
4
Motion sensor
7320.570
4
Digital input module
7320.580
4
Digital relay output module
7320.590
4
Voltage monitor
7320.600
4
Voltage monitor with switch output
7320.610
4
48 V voltage monitor
7320.620
4
Leakage sensor
7320.630
4
Note:
Further explanations concerning the various setting options and features are
available in the CMC-TC system documentation.
Menu option
Explanation
Server-in
temperature
Display of the average of the three server-in temperatures from the
sensors on the heat exchanger.
Alarms /
Warnings
Display of the alarm and warning message in plain text (cf.
Chapter 6.6.1, "General").