Operating and Maintenance Instructions – 2 Safety instructions
Rittal Liquid Cooling Package Plus
2.3
Service and technical staff
The installation, commissioning, maintenance and repair of this unit may only
be carried out by qualified mechanical and electro-technical trained personnel.
Only properly instructed personnel may carry out service on a unit while in ope-
ration.
Danger! Injury due to falling loads!
Do not stand under suspended loads when transporting the unit with a
hoist trolley, a forklift, or a crane.
Caution! Risk of malfunction or damage!
Do not modify the unit! Use only original spare parts!
Caution! Risk of malfunction or damage!
Proper and flawless unit operation can only be ensured when it is ope-
rated under the intended ambient conditions. As far as possible, be
sure that the ambient conditions for which the unit is designed are com-
plied with, e.g. temperature, humidity, air purity.
Caution! Risk of malfunction or damage!
All media necessary for the control system, e.g. cooling water, must be
available during the entire operating time.
Caution! Risk of malfunction or damage!
In order to avoid frost damage, the minimum permissible input water
temperature of +6 °C must not be undercut at any point in the water cy-
cle!
It is vital that the manufacturers’ consent is obtained before adding
anti-freeze!
Caution! Risk of malfunction or damage!
During storage and transportation below freezing point, the water cycle
should be drained completely using compressed air!
Caution! Risk of malfunction or damage!
Only set the temperature control setpoint as low as is strictly necessa-
ry, since the danger of condensation through undercutting the dew
point increases with a falling water inlet temperature!
Ensure that the enclosure is sealed on all sides, particularly at the cable
entry (condensation)!