Operating and Maintenance Instructions – 6 Installation – "Getting Started"
Rittal Liquid Cooling Package Plus
6.4
Connecting the
Liquid Cooling Package
Plus
6.4.1 Electrical connection
6.4.1.1 General
The Liquid Cooling Package Plus' power supply is made over either a separate
3-pole or 5-pole supply, as desired. The device is always delivered with a 5-
pole mains connection socket so that the user can attach a connection cable
with a mains plug (3-pole or 5-pole) that corresponds to local requirements. Re-
levant connection cables available from Rittal accessories (Model No. DK
7856.025 or DK 7856.026).
Two of fan modules installed in the Liquid Cooling Package Plus are on a sepa-
rate phase.
If the Liquid Cooling Package Plus is connected to the mains using a 3-pole,
single-phase, 230 V connection cable (L, N, PE; DK 7856.026), one of the pha-
ses must be bridged to the other two. This is already implemented in the 5-pole
plug.
Note:
Please keep this electrical documentation readily available so that it is al-
ways on hand when needed. This is the only documentation which is autho-
ritative for the unit.
Caution!
Work on electrical systems or equipment may only be carried out by an
electrician or by trained personnel guided and supervised by an electri-
cian. All work must be carried out in accordance with electrical engi-
neering regulations.
The unit may only be connected after the above-named personnel have
read this information.
Use insulated tools.
The connection regulations of the appropriate power company are to be
followed.
The voltage values shown in the wiring plan or on the rating plate must
match the mains voltage.
The pre-fuse specified in the wiring plan or on the rating plate should
be provided as power protection. The unit must be individually fused.
The unit must be connected to the mains via an isolating device which
ensures at least 3 mm contact opening when switched off.
The mains connection may only be made using the connection cable
which extends from the unit.
No additional control equipment may be connected upstream of the de-
vice at the supply end.