Operating and Maintenance Instructions – 6 Installation – "Getting Started"
Rittal Liquid Cooling Package Plus
6.5
Cooling operation and
control behaviour
If the LCP Plus is provided with power, the control valve controls the cooling wa-
ter flow according to the established setpoint temperature. For more detailed
explanations, please refer to Chapter 4.2, "Function".
6.5.1 Cooling output
The following diagrams show the cooling output of the Liquid Cooling Package
Plus in [kW], depending on the cooling water flow [l/min] and the air inlet tem-
perature [°C] for various flow temperatures. They are meant to assist the ope-
rator in the planning phase to determine the water circuit necessary for the
system.
Fig. 42:
Cooling output of the Liquid Cooling Package Plus, with flow temperature 10 °C
10
15
20
25
30
35
10
15
20
25
30
35
40
45
Air admittance 20˚C
Air admittance 25˚C
Inlet temperature [°C]
Co
olin
g output
[Watt]