A3346302IT74-GB
36
6. Make sure the bypass fuses F2 are inserted (front of Module);
7. Close internal and external battery fuses/breaker(if available);
8. Press simultaneously both “ON/OFF” Buttons to start-up UPS.
LCD panel must display: “LOAD DISCONNECTED PARALLEL SWITCH OPEN” and
the LED-indicator will appear as shown below:
LED Indicator
Colour
LINE 1
Green
LINE 2
Green
BYPASS
OFF
INVERTER
Green
BATTERY
Green
9. Transfer load to mains and inverter for testing using submenu COMMANDS;
10. Transfer Load to Bypass-Mode by means of COMMAND “LOAD TO BYPASS”
11. Verify the status (Load on Bypass, Eco-Mode) by checking the LED-indicators as
shown below:
LED Indicator
Colour
LINE 1
Green
LINE 2
Green
BYPASS
Green
INVERTER
OFF
BATTERY
Green
12. Close Parallel Isolator (IA2);
13. Open Maintenance Bypass (IA1) by turning it to position “OFF”. The load is now
supplied by the static bypass.
14. Transfer load to Inverter-Mode by means of COMMAND “LOAD TO INVERTER”. On
LCD: “LOAD PROTECTED” will appear.
THE LOAD IS NOW PROTECTED BY THE PMC