A3346302IT74-GB
8
3 Installation
3.1 INTRODUCTION
This chapter contains all the necessary information for the correct unpacking, positioning, cabling
and installation of the
PMC
.
ALL THE OPERATIONS IN THIS SECTION MUST BE PERFORMED BY
AUTHORISED ELECTRICIANS OR BY QUALIFIED PERSONNEL.
RITTAL will take no responsibility for any personal or material damage caused
by incorrect cabling or operations or activities, which are not carried out as per
the instructions contained in this manual.
3.1.1 Receipt of the UPS
Upon receiving the UPS, carefully examine the packing container and the UPS for any sign of
physical damage. In case of rupture or suspect inform immediately:
a) The carrier and
b) RITTAL GmbH & Co. KG.
Ensure that the received UPS corresponds to the material indicated in the delivery note.
The packing container of the
PMC
protects it from mechanical and environmental damage. To
increase its protection the UPS is wrapped with a plastic sheet.
3.1.2 Nameplate
The technical specifications of the
PMC
are provided on the nameplate, which is situated at the
front of the UPS. Check if it corresponds to the purchased material mentioned in the delivery
note.
3.2 UNPACKING
When unpacking the UPS observe the "FRAGILE" and "ARROW" on the packing container.
Perform the following steps to unpack the UPS:
•
Cut wrappers and remove packing container by pulling it upwards;
•
Remove the plastic cover from the UPS;
•
Remove pallet from the UPS;
•
Retain the packaging materials for future shipment of the UPS;
•
Examine the UPS for any sign of damage. Notify your carrier or supplier immediately if
damage is apparent.
•
Open the UPS-door and make sure that all the UPS-Mudules are appropriately fitted
in their UPS-Compartment and if the UPS system is provided without a UPS-module
make sure that the empty UPS-compartment is correctly covered with the UPS-
compartment protection cover.
3.3 BATTERIES
The standard batteries of the
PMC
are sealed, maintenance-free batteries, mounted in an
external battery cabinet and will typically be connected when the UPS is commissioned.
The battery life depends very much on the ambient temperature. A temperature range between
+18° and +23°C will achieve the optimum battery life.
If the UPS is delivered without batteries, RITTAL is not responsible for any damage or
malfunctioning caused to the UPS by incorrect wiring.
!