40
UPS system directly without charging it but the stored energy time
may then be shorter than the nominal value specified.
8)
Set the O/P switch on the back panel to position „ON“.
9)
Press the On button „I“ on the front panel.
Note:
The INVERTER LED lights up after 10 seconds. The BYPASS
LED then goes out and the ventilation system switches on. The
UPS system is now operating correctly.
10)
Test the function of the UPS system by either pressing the On
button „I“ or disconnecting the input of the UPS system from the
power supply.
Caution!
The output sockets of the UPS system may still be electrically
live even if the power supply system has been disconnected or if
the I/P switch is in position OFF.