5 Installation
EN
20
Rittal enclosure cooling unit
In the same way, insert the two corner brackets with
nuts onto the grub screws at the bottom and secure
(torque = 5 Nm).
Fig. 38:
Secure with corner brackets at the bottom
Insert one spring clip half-way up the rear of the cool-
ing unit on both the left and right.
Fig. 39:
Secure with spring clips
For SK 317880x and SK 317980x: Release the locator
clip at the top left and, where applicable, insert it into
the rear of the device for cable fixing and routing.
Fig. 40:
Release the locator clip (for SK 317880x and
SK 317980x)
For SK 31848x0: Release the two locator clips at the
top and insert one of the clips into the rear of the de-
vice for cable fixing and routing. The second clip may
likewise be inserted into the top rear of the device.
Fig. 41:
Release the locator clips (for SK 31848x0)
SK 317880x and SK 317980x
Bring the louvred grille close to the device.
Connect the connector at the bottom of the display.
Place the louvred grille onto the mounting clips at the
top and bottom, keeping it as straight as possible, and
press it fully onto the cooling unit.
SK 31848x0
Holding the lower louvred grille at an angle from
above, engage it fully with the bottom clips.
Insert the range limiters for the bottom louvred grille
into their holders on the left and right of the device.
Carefully push the connection cable section by section
into the groove in the lower louvred grille.
Insert the connector into the bottom of the display.
Position the top louvred grille onto the mounting clips.
Snap the bottom louvred grille completely onto the
cooling unit.
5.3.6
Connect the condensate water discharge
There is a condensate water evaporator fitted in the ex-
ternal circuit of the cooling unit. With an enclosure con-
nected, this condensate water evaporator may typically
evaporate condensate water volumes of up to 100 ml/h.
If larger quantities of condensate water are produced, a
condensate water discharge hose may additionally be
fitted. This hose allows condensate water to be routed
out of the cooling unit pressurelessly. A suitable hose is
available as an accessory from Rittal (see section 13
"Accessories").
Please follow the instructions given below:
– The hose must be laid with an adequate and constant
gradient to prevent siphoning.
– The hose must be laid without any kinks.
– If extended, the cross-section of the hose must not be
reduced.
CLICK!
1.
2.
1.
2.