APPENDIX
Installation Instructions for SIS Bus Bar Systems A2MS001EN revision R05
110 / 130
Electrical connections
………
Earthing (except for earthing
nut*)
M
A
[Nm]
M8
16
M10
30
Earthing
– earthing nut*
M
A
[Nm]
M10
20
*See Appendix E on page 114 to check whether earthing via earthing nut applies or not.