INSTALLATION
Installation Instructions for SIS Bus Bar Systems A2MS001EN revision R05
53 / 130
Fig. 29: Cleaning the insides of the
connection sleeve
1.
Use acetone and a lint-free rag to thoroughly
clean the inside of the connection sleeve (Fig. 29).
Fig. 30: Cleaning sealing surfaces
2.
Use acetone and a lint-free rag to thoroughly
clean the outside of the connection sleeve, especially
the area of the seal (Fig. 29).
3.
Enter the serial number of the connection sleeve
and of the bus bars in the general drawing.
4.
Clean the bus bar segments onto which the
connection sleeve is pushed.
Fig. 31: Seal glued
5.
Place the sealing rings on the connection sleeve
on both sides, aligning the holes in the ring over the
thread holes on the ends of the connection sleeves,
and secure them with adhesive tape or super glue (Fig.
31).
6.
Slide the connection sleeve onto the bar,
positioning the connection sleeve so there is sufficient
space for installation of the flexible connectors (Fig.
32).
Fig. 32: Connection sleeves on bar
7.
If necessary, remove the parts of the fixation
system. In this case, remove a bearing as seen in Fig.
32.
If the bar does not remain exactly in position as a
result of its dead weight, it must be secured with
suitable measures until the bearing can be re-
attached after the installation of the flexible
connectors and the closing of the connection sleeve.
This can best be achieved by securing with ratchet
slings or affixing/supporting with an installation strut.